zeek-slmp

zeek-slmp

A Spicy-based Zeek analyzer for SLMP (SeamLess Message Protocol), the message protocol used by Mitsubishi Electric MELSEC controllers and other SLMP-compatible devices. It parses the binary encoding of 3E, 4E and station number extension frames over TCP and UDP and writes slmp.log.

The package is meant for research and interoperability: passive visibility into SLMP traffic on networks you are authorised to monitor. It only reads traffic; it never sends anything.

Author: John B Joseph

What it parses

  • Frame types (binary code only):
    • 3E request/response (subheader 50 00 / D0 00)
    • 4E request/response (subheader 54 00 / D4 00, with serial number)
    • station number extension request/response (subheader 68 00 / E8 00, with serial number and extension station number)
  • Header: request destination network number, station number, module I/O number, multidrop station number, request data length, monitoring timer.
  • Command and subcommand for every request. All commands in the manual's command list get a name; unknown codes are logged as unknown-0x.....
  • Device fields decoded for:
    • Device Read 0401 and Device Write 1401, subcommands 0000-0003 (head device, device code, number of points);
    • Device Read Random 0403, subcommands 0000/0002 (number of entries and the first device);
    • Device Write Random 1402, subcommands 0000-0003 (number of entries and the first device).
  • Remote Run 1001 mode and clear mode. Remote Stop 1002, Pause 1003, Latch Clear 1005 and Reset 1006 are logged by name.
  • Read Type Name 0101: model name and model code from the response.
  • Responses: end code; for error responses, the command and subcommand echoed by the device.

slmp.log

One line per request/response pair. 4E and station number extension frames are paired by serial number; 3E frames (no serial number) are paired in order of arrival on the connection. A request with no response is logged when the connection ends (status = no_response); a response with no matching request is logged on its own (status = no_request).

Field Type Description
ts time Time of the request (or of the response, if no request was seen)
uid, id string, conn_id Zeek connection identifiers
proto transport_proto tcp or udp
frame_type string 3E, 4E or station-ext
serial count Serial number (4E and station-ext only)
network count Request destination network number
station count Request destination station number
module_io string Request destination module I/O number, hex (for example 0x03ff)
multidrop count Request destination multidrop station number
ext_station count Extension station number (station-ext only)
monitoring_timer count Monitoring timer in 250 ms units (0 = wait forever)
command string Command name, for example Device Read or Remote Stop
command_code string Command code, hex
subcommand string Subcommand, hex
device string Device name, for example D, M, X (decoded device commands only)
head_device count Head device number as a number
address string Device and number in the usual notation, decimal or hex by device, for example D100, X20, W100
points count Number of points; for random read/write, the number of entries
run_mode string Remote Run mode, hex (0x0001 forced execution not allowed, 0x0003 allowed)
clear_mode count Remote Run clear mode (0, 1 or 2)
model_name string Model name from a Read Type Name response
model_code string Model code from a Read Type Name response, hex
end_code string End code, hex; 0x0000 means success
status string ok, error, no_response or no_request
rtt interval Time from request to response

Example (from the test trace testing/Traces/slmp_3e_tcp.pcap, some columns left out):

frame_type command             subcommand device head_device address points end_code status
3E         Read Type Name      0x0000     -      -           -       -      0x0000   ok
3E         Device Read         0x0000     D      100         D100    3      0x0000   ok
3E         Device Write Random 0x0001     M      50          M50     2      0x0000   ok
3E         Remote Run          0x0000     -      -           -       -      0xc059   error

The analyzer confirms the protocol after the first complete frame. After a frame it cannot parse (unknown subheader, non-zero fixed fields, a length that does not match the data) or a gap in a TCP stream, it skips ahead to the next byte pair that can start a frame and carries on, so one bad frame does not end parsing for the rest of a long polling connection. If no valid frame follows, Zeek reports a protocol violation through analyzer_violation_info and analyzer.log.

An error response that carries only the end code, without the error information block, is logged with its end code and status error.

On a TCP gap, 3E requests still waiting for a response are logged as no_response, because 3E frames have no serial number and a missing frame would otherwise shift every later pair.

Ports

SLMP has no fixed port: the port is set in each device's parameters. The analyzer is attached by content, using the dynamic protocol detection signatures in scripts/dpd.sig: a request subheader from the client and a matching response subheader from the server. No port is registered by default, so unrelated services on common SLMP ports (HTTP on 5000, RTP on 5004/5005) do not reach the analyzer.

Because detection needs the response, the first request on a connection is handed to the analyzer when its response arrives: that line's ts is the response time and its rtt is unset. Traffic seen in one direction only (for example requests without responses) is not detected. To attach the analyzer to a port unconditionally:

redef SLMP::ports_tcp += { 5000/tcp };
redef SLMP::ports_udp += { 5000/udp };

Installation

With zkg, from a local clone:

zkg install ./zeek-slmp

Manual build (needs spicyz, which ships with Zeek 6 and later, and CMake):

mkdir -p build && cd build && cmake .. && cmake --build .
zeek -r capture.pcap ./build/slmp.hlto ./scripts

Tests

cd testing && btest -c btest.cfg

The test captures in testing/Traces are synthetic. Each .pcap is generated by the Python script with the same name (slmp_3e_tcp.py writes slmp_3e_tcp.pcap, and so on), using slmp_pcaplib.py and the standard library only. No traffic from a real device is included.

Test Covers
availability Both analyzers are registered
trace-3e-tcp 3E over TCP: Read Type Name, batch read/write (Q/L and iQ-R formats), random read/write, remote STOP and RUN, an error end code, two frames in one segment, a frame split across segments
trace-4e-udp 4E over UDP: serial number pairing with out-of-order responses, remote PAUSE/latch clear/RESET, a request without a response, a response without a request, a station number extension frame
malformed Unknown subheader, non-zero fixed field, request data length larger than the datagram
not-slmp HTTP on 5000/tcp and RTP on 5004/udp do not reach the analyzer; SLMP on 6000/tcp and 6001/udp is detected by content
recovery Parsing continues after a missing request segment, a missing response segment, an error response without the error information block, and junk between frames

Sources

The protocol was implemented from the publicly downloadable manual only:

  • Mitsubishi Electric, SLMP Reference Manual, SH(NA)-080956ENG, revision N (October 2025), downloaded 2026-11-13 from https://dl.mitsubishielectric.com/dl/fa/document/manual/plc/sh080956eng/sh080956engn.pdf, SHA-256 3abef70db23577dded014af0f7fabd5d340284d590ff28dceb4442d8aea70ed4. Chapter 4 (message format) and sections 5.1, 5.2 and 5.6 (command list, device access, remote control).

No text from the manual is copied into this repository beyond command names, device names and numeric codes.

Related work: nttcom/zeek-parser-CCLinkTSNSLMP parses SLMP frames carried by CC-Link IE TSN on UDP ports 45238/45239 and logs the command and subcommand. This package covers the MELSEC Ethernet 3E/4E frames on user-configured ports and decodes device access, remote control and end codes.

The files cmake/FindSpicyPlugin.cmake, testing/Scripts/get-zeek-env, testing/Scripts/diff-remove-timestamps and testing/Files/random.seed come from zeek/package-template (BSD-3-Clause).

Limitations

  • ASCII code frames are not parsed; they raise a protocol violation.
  • Device extension specification subcommands (0080-0083), block read/write (0406/1406), monitor registration, label, memory, extend unit, file, remote password and self test commands are logged by name and subcommand only; their data is not decoded.
  • Random read/write log the first device and the number of entries, not every device.
  • Write data and read data values are not logged.
  • End codes are logged as numbers. Their meaning depends on the device and is documented in each device's manual, so no names are assigned.
  • 3E pairing assumes responses arrive in request order on a connection, as the protocol has no serial number for 3E. Pipelined 3E requests answered out of order would be mispaired.
  • The analyzer was tested only against the synthetic captures in this repository, not against traffic from real controllers.
  • The station number extension frame was implemented from the manual's format description; it is covered by one synthetic test.

Development note

Parts of this package, including the capture generator scripts, were written with the help of an AI coding assistant.

License

BSD-3-Clause, see LICENSE.